Created with Pixso.

YCSS-101 Single Phase Standard Power Source

YCSS-101 Single Phase Standard Power Source

Markenbezeichnung: GENY
Modellnummer: YCSS-101
MOQ: 1 STK
Preis: negotiate rates
Zahlungsbedingungen: T/T,L/C,D/P,T/T
Versorgungsfähigkeit: 5 Sätze / 1 Monat
Ausführliche Information
Herkunftsort:
China
Zertifizierung:
ISO, CE
Ausgangsspannung der Prüfung:
0V bis 480V
Leistung der Ausgangsspannung:
Max.25VA
Leistung des Prüfstroms:
1mA-120A
Phasenwinkelbereich:
0 -- 360°
Häufigkeit:
45 Hz bis 65 Hz
Verpackung Informationen:
Sperrholzkisten
Versorgungsmaterial-Fähigkeit:
5 Sätze / 1 Monat
Produkt-Beschreibung

YCSS-101 Single Phase Standard Power Source


Guangzhou GENY Electric Co. Ltd. YCSS-101 Single Phase Standard Power Source is an essential calibration instrument for ammeters, wattmeters, energy meters, and power frequency phase meters, widely used in metrology departments, power utilities, industrial and mining enterprise calibration labs, and meter manufacturing facilities.


Features & Functions


  1. Portable & Integrated
    Compact design with integrated reference standard and power source. Perfect for on-site testing anywhere.
  2. High Performance-Price Ratio
    Affordable yet powerful, offering great value for money.
  3. Wide Output Range
    Covers 0V–480V voltage and 1mA–120A current, suitable for various meters.
  4. Dual Calibration Capability
    Supports simultaneous calibration of two meters or active/reactive power calibration for one meter, increasing efficiency.
  5. User-Friendly Operation
    Manual keyboard and PC automation options for flexible use.
  6. Multiple Communication Ports
    Internet and RS 232 interfaces for easy data transfer and management.

Specifications



Voltage

Test voltage output

0V-480V

Resolution

1mV

Power of the voltage output

Max.25VA

Setting accuracy

0.05% at 50-400V

Stability

0.03%/h (integration time 150s)

Harmonics

2nd-41st free programmable

Distortion factor

<0.2% for linear resistance load



Current

Test current output

1mA-120A

Setting accuracy

0.05% at 1mA-120A

Power of the voltage output

Max.120VA

Stability

0.003%/h (Integration time 150s)

Resolution

0.2mA

Distortion factor

<0.2% for linear resistance load

Harmonics

2nd-21st free programmable



Phase angle

Frequency

Range

0°-360°

Range

45Hz-65Hz

Resolution

0.001°

Resolution

0.0001Hz

Setting accuracy

0.005°



Pulse output

High frequency output

>20A FH=10^7; >2A FH=10^8; >0.2A FH=10^9

Pulse Input

Input channel

2

Input frequency

Max.100kHz

Other

Voltage Supply

220V±10% 50/60Hz±2Hz

Dimensions (W×H×D) (mm)

484x184×543

Ambient temperature

-10°C-+40°C

Weight (kg)

15

Relative humidity

35%-85%

Conformity

CE conform