logo

Einzelheiten zu den Produkten

Created with Pixso. Haus Created with Pixso. Produits Created with Pixso.
Prüfgeräte für stationäre Zähler
Created with Pixso.

Three Phase I-P Close Link Meter Testing Equipment for calibration 6 MTUs

Three Phase I-P Close Link Meter Testing Equipment for calibration 6 MTUs

Markenbezeichnung: GENY
Modellnummer: YC1893d
MOQ: 1 PCs
Preis: Verhandlungsfähig
Zahlungsbedingungen: L/c, t/t, d/p
Versorgungsfähigkeit: 100/Jahr
Ausführliche Information
Herkunftsort:
CHINA
Zertifizierung:
ISO, CE
Genauigkeitsklasse der IKT:
00,05 auf 0.01
Ausgangsspannung der Prüfung (phasenneutral):
3x ((24V~288V) ((oder angepasst)
Frequenzbereich:
45Hz~65Hz
Spannungsversorgung:
3x220/380V ± 10% ((oder angepasst) 50/60Hz ± 2Hz
Verpackung Informationen:
Sperrholzfall
Versorgungsmaterial-Fähigkeit:
100/Jahr
Hervorheben:

Three Phase meter testing equipment

,

I-P Close Link calibration tool

,

Stationary meter test equipment with warranty

Produkt-Beschreibung

Three Phase I-P Close Link Meter Testing Equipment for calibration 6/12/24/48 MTUs


Guangzhou GENY Electric Co., Ltd. is a professional manufacturer of power metering and testing equipment, established in 2002. With the registered brand "GENY", we are known for reliable quality, innovative design, and strong industry expertise.

We focus on R&D and production of electric meter testing systems, serving utilities and industrial users with trusted solutions.


The test bench is a high-precision three-phase meter test system with an accuracy class of 0.02%, capable of testing up to 6 meters simultaneously. It integrates ICTs (Information and Communication Technologies) and features a multi-serial port communication system for efficient parallel testing of smart meters.



Voltage

3×240±15%

Frequency

50 Hz ±15%

Power capacity

> 6 kVA

Power efficient(at full load)

≥85%

Ambient temperature

-10 °C -- +40 °C

Relative humidity

35% -- 85%


Voltage

Test voltage output (Phase-Neutral)

3×(24 V – 480 V) or 600 V F-F customized

Power of the voltage output

3×100VA

Resolution

Better than 0.01% of full scale value of range

Setting accuracy

Better than 0.02% at the final range value

Stability

Better than 0.005%/h (integration time 150 s)

Load regulation from 0-max. load

< 0.01%

Distortion factor

< 0.3% for linear resistance load

Harmonics

2nd – 21st free programmable

Current

Test current output

0.3 mA – 120 A

Power of the current output

3×150VA

Resolution

Better than 0.01% of full scale value of range

Setting accuracy

Better than 0.02% at the final range value

Stability

Better than 0.005%/h (integration time 150 s)

Load regulation from 0-max. load

< 0.01%

Distortion factor

< 0.3% for linear resistance load

Harmonics

2nd – 21st free programmable

Phase angle

Range

0 -- 360°

Resolution

0.01°

Setting accuracy

0.1°

Frequency

Range

45 Hz – 65 Hz

Resolution

0.01 Hz



Three Phase I-P Close Link Meter Testing Equipment for calibration 6 MTUs 0